NOT JUST CLEAN BUT SPOTLESS WOLF Hygiene solutions
WOLF air handling units are designed strictly in line with DIN Standard 1946, Part 4, and built with the greatest of care. For engineers and developers this guarantees straightforward design, problem-free approval and safe operation in hospitals, clean rooms and areas with the strictest hygiene requirements.
In addition to the general standards and regulations to be observed, WOLF hygiene units have been certified as complying with and implementing the design and structural requirements of DIN 1946, Part 4, as part of the TÜV SÜD type test.
Strict adherence to design regulations
to DIN 1946, Part 4
Smooth, hygienic
surfaces
Interior surfaces can be cleaned leaving no residue
All gaps and grooves are sealed with closed-cell, microbiologically inexploitable and harmless sealing materials
Door seals removable
for cleaning purposes
All components accessible from both sides
Lights and sight glasses (optionally with blackout) integrated in service and function units
Stainless steel
filter mounting frame
with foam seal, gapless
Insulated
3D condensate pan
with all-round slope to drain for complete draining.
Mist eliminator with stainless steel frame, can be fully dismantled for cleaning
Inside of floor panels in stainless steel 1.4301
Insides of wall and top panels with powder coating (optional stainless steel 1.4301)
Filter mounting frame and slide-in rails
in stainless steel 1.4301
Filter categories F6–F9, H10–H13 with test certificate
Heating coil
in Cu/Al
with coated frame or stainless steel 1.4301 and minimum fin spacing of 2.0 mm
Cu/Al cooling coil with frame in stainless steel 1.4301, copper receiver, coated fins and minimum fin spacing of 2.5 mm
Free-running EC fans in hygiene version with coated impeller, completely accessible and easy to clean