General data | | | | | |
| Rated heating output at 80/60 °C | kW | 366.7 | 434.7 | 511.6 | 584.4 |
| Rated heating output at 50/30 °C | kW | 392 | 467.1 | 549.2 | 626.6 |
| Rated heat input | kW | 371.2 | 443.6 | 521 | 593.9 |
| Lowest heating output (modulating) at 80/60 °C | kW | 58.5 | 70.7 | 84.5 | 96.7 |
| Lowest heating output (modulating) at 50/30 °C | kW | 64.2 | 78.7 | 94 | 106.8 |
| Lowest heat input (modulating) | kW | 59.5 | 73.2 | 86.8 | 98.5 |
| Heat input modulation range | % | 17-100 | 17-100 | 17-100 | 17-100 |
| Amount of condensate at 40/30 °C | l/h | 39 | 46 | 52 | 59 |
| Condensate pH value | | approx. 4,0 | approx. 4,0 | approx. 4,0 | approx. 4,0 |
| Water capacity of the heating water heat exchanger | l | 50 | 56 | 62 | 68 |
| Max. permissible boiler pressure | bar | 6 | 6 | 6 | 6 |
| Max. permissible flow temperature | °C | 90 | 90 | 90 | 90 |
| Available gas fan draught | Pa | 150 | 150 | 150 | 150 |
| Standby losses excess temperature 30 / 50 K | % | 0,11 / 0,18 | 0,10 / 0,17 | 0,09 / 0,15 | 0,09 / 0,14 |
| Flue gas temperature 80/60-50/30 at Qmax | °C | 65-35 | 65-35 | 65-35 | 65-35 |
| Flue gas temperature 80/60-50/30 at Qmin | °C | 60-30 | 60-30 | 60-30 | 60-30 |
| Max. flue gas mass flow rate | g/s | 156.3 | 185.2 | 225.3 | 247.4 |
| Flue gas category to DVGW G 635 | | G 52 | G 52 | G 52 | G 52 |
| Heating water pressure drop with 20 K spread | mbar | 120 | 113 | 126 | 118 |
| IP rating | | IP20 | IP20 | IP20 | IP20 |
| Sound power to EN 15036 Part 1, room sealed | dB(A) | 61 | 66 | 68 | 68 |
| Sound pressure level 1 m in front of MGK-2, room sealed 2) | dB(A) | 44 | 49 | 50 | 50 |
| Sound power to EN 15036 Part 1, open flue | dB(A) | 78 | 82 | 84 | 84 |
| Sound pressure level 1 m in front of MGK-2, open flue 2) | dB(A) | 60 | 64 | 65 | 65 |
Efficiency | | | | | |
| η 80/60 at Qmax | % | 98.8 | 98 | 98.2 | 98.4 |
| η 50/30 at Qmax | % | 105.6 | 105.3 | 105.4 | 105.5 |
| η TR30 at 30% | % | 107.8 | 108.9 | 108.6 | 107.6 |
Standard seasonal efficiency [to DIN] | | | | | |
| at 40 / 30°C | % | 109.9 | 110.1 | 110.3 | 110.4 |
| at 75 / 60°C | % | 106.4 | 106.4 | 106.3 | 106.3 |
| Total height | A mm | 1460 | 1460 | 1460 | 1460 |
| Total width / width excl. gas/air connection | B mm | 1860/1295 | | | |
| Total depth / depth excl. casing | C mm | 850 / 790 | 850 / 790 | 850 / 790 | 850 / 790 |
| Flue diameter | mm | 250 | 250 | 250 | 250 |
| Combustion air supply | mm | 200 | 200 | 200 | 200 |
| Heating flow | DN | 80 PN6 | 80 PN6 | 80 PN6 | 80 PN6 |
| Heating return | DN | 80 PN6 | 80 PN6 | 80 PN6 | 80 PN6 |
| Gas connection | R | 2“ | 2“ | 2“ | 2“ |
| Air/flue gas routing | Type | B23, B23P, C33, C43, C53, C63, C83, C93 | | | |
Gas supply details: | | | | | |
| Natural gas E/H (net cv = 9.5 kWh/m³ = 34.2 MJ/m³) | | 39.1 | 46.7 | 54.8 | 62.5 |
| Natural gas LL (net cv = 8.6 kWh/m³ = 31.0 MJ/m³) | | 43.2 | 51.6 | 60.6 | 69.0 |
| Gas supply pressure: natural gas E/H/LL | mbar | 20 | 20 | 20 | 20 |
Weight | | | | | |
| Total weight (empty) | kg | 390 | 420 | 450 | 480 |
Electrics | | | | | |
| Electrical connection for fuse protection | V~/Hz | 1~ NPE / 230VAC / 50Hz / 10A/B alternativ: 3~ NPE / 400VAC / 50Hz / 10A/B
|
| Output heating circuit pump/ZHP fuse | V~/Hz | 1~ NPE / 230VAC / 50Hz / 4A alternativ: 3~ NPE / 400VAC / 50Hz / 4A
|
| Power consumption (partial load/full load) | W | 42 - 410 | 45 - 490 | 48 - 580 | 50 - 660 |
| Standby power consumption | W | 8 | 8 | 8 | 8 |