Output / input | | | |
| Rated heating output at 80/60 °C | kW | 700 | 931 |
| Rated heating output at 50/30 °C | kW | 752 | 1000 |
| Rated heat input | kW | 710 | 942 |
| Lowest heating output (modulating) at 50/30 | kW | 133 | 174 |
| Lowest heating output (modulating) at 80/60 | kW | 119 | 157 |
| Lowest heat input (modulating) | kW | 122 | 160 |
| Heat input modulation range | % | 17-100 | 17-100 |
Efficiency | | | |
| h 80/60 at Qmax | % | 98.7 | 98.8 |
| h 50/30 at Qmax | % | 106 | 106.2 |
| h TR30 at 30% | % | 108.8 | 110 |
Standard seasonal efficiency [to DIN] | | | |
| at 40 / 30°C | % | 110.1 | 110.1 |
| at 75 / 60°C | % | 106.3 | 106.3 |
Dimension | | | |
| Total height | A mm | 1460 | 1460 |
| Total width / width excl. gas/air connection | B mm | 2265 / 1700 | 2265 / 1700 |
| Total depth / depth excl. casing | C mm | 970 / 950 | 970 / 950 |
| Flue diameter | mm | 250 | 250 |
| Ventilation air connection | mm | 200 | 200 |
Weight | | | |
| Total weight | kg | 625 | 680 |
Connections | | | |
| Heating flow | DN/PN | 100/6 | 100/6 |
| Heating return | DN/PN | 100/6 | 100/6 |
| Gas connection | R | 2,5"" | 2.5 |
| Gas category | | I2ELL | |
Gas supply details | | | |
| Natural gas E/H (9.45 kWh/m³) | m³/h | 75 | 99.5 |
| Natural gas LL (8.82 kWh/m³) | m³/h | 80.3 | 106.6 |
| Gas supply pressure | mbar | 20 | 20 |
Heating circuit | | | |
| Water capacity of the heating water heat exchanger | l | 80.5 | 92.6 |
| Max. total pressure | bar | 6 | 6 |
| Max. flow temperature | °C | 90 | 90 |
| Heating water pressure drop with 20 K spread | mbar | 127 | 123 |
| Standby losses excess temperature 30 / 50 K | % | 0,07 / 0,13 | 0,06 / 0,10 |
Flue gas | | | |
| Type of flue installation | Type | B23, B23P, C43, C53, C63, C83, C93 | |
| Max. flue gas temperature | °C | 80 | 80 |
| Condensate pH value | | approx. 4,0 | approx. 4,0 |
| Max. flue gas temperature 80/60 – 50/30 at Qmax | °C | 65-42 | 65-40 |
| Max. flue gas temperature 80/60 – 50/30 at Qmin | °C | 62-32 | 62-32 |
| Max. flue gas mass flow rate | g/s | 307 | 407 |
| Amount of condensate at 40/30 °C | l/h | 77 | 93 |
| Flue gas category to DVGW G 635 | | G52 | G52 |
Gas fan | | | |
| Available gas fan draught | Pa | 200 | 250 |
| Electrical connection | | 1~ NPE / 230VAC / 50Hz / 10A/B | 3~ NPE 400VAC/50Hz |
| Electrical connection alternatively | | 3~ NPE / 400VAC / 50Hz | - |
| Phases / voltage / frequency | | 1 ~ NPE / 230 VAC / 50 Hz | 3 ~ NPE / 400 VAC / 50 Hz |
| Fuse protection | | 16 A/B | 16 A/C |
| Heating circuit pump output / ZHP / fuse protection | | 1~ NPE / 230VAC / 50Hz / max. 7A | |
| alternatively | | 3~NPE / 400VAC / 50Hz / max. 7A | |
| Power consumption (partial load/full load) | W | 50 - 850 | 60 - 1835 |
| Power consumption on standby | W | 8 | 11 |
| IP rating | | IP20 | |
Noise emissions | | | |
| Sound power to EN 15036 Part 1, room sealed | dB(A) | 67.7 | 73.3 |
| Sound power to EN 15036 Part 1, open flue | dB(A) | 85.1 | 83.5 |
| Sound pressure level in room, 1 m in front of MGK-2, room sealed 1) | dB(A) | 65-70 | 70-75 |
| Sound pressure level in room, 1 m in front of MGK-2, open flue 1) | dB(A) | 82-87 | 80-85 |